Table 2. Differences measuring leakage inductance for the same sample
💡 Note that the leakage inductance is the one of the secondary, as it is measured reflected back to the primary. That is easily done by shorting the secondary and taking an inductance measurement of the primary. The two values are measured at 2 different frequencies, so I couldn’t make a good comparison.
Then I remembered that the controller board mentioned could tolerate up to 5uH of leakage. The original transformer had a leakage inductance of approximately 4.7uH. With 6-7.5uH the design was probably triggering the controller protection, and thus the shutdown after 40-45W.
🤔 OK, that might be the reason why. But what’s really happening with leakage inductance? What’s the true value? Pfff, an engineer can’t have a relaxed day, we have to face challenges every day….
🙌 Time for action!
I took the transformer completely apart and rewind it using round wires. This time I didn’t care for isolation, as functional isolation would be enough. My focus was to make a revision to get the leakage as low as possible and to see if that was the limitation of the test, but also make sure that no mistakes were made in the assembly.
🫣 Don’t blame me for not trusting other people in debugging. In these situations I don’t trust anything (not even myself…) that I can’t prove, so I had to make a new sample to eliminate every other possibility. I also ditched the LCR meter and brought the big guns: my frequency response analyser is more than capable to give us a clear idea about the leakage-frequency dependency.
As Archimedes had his “eureka!” (“Εύρηκα” in Greek ) moment, I had mine while setting up the equipment testing! I asked myself: "How did I shorted the secondary winding?". And my answer was: "Bending those 30mm wires you can see in Figure 1".
🫵 Aha! Got you!
Look at Figure 2. That’s the difference in leakage measured using different lengths of shorting wire at the secondary transformer pins.